- Visual Inspection
- To check the cracks, rust or chipping.
- To check the Serial Number.
- To check the Level of Oil.
- To check the leakage/seepage of Oil.
- To check the Markings on transformers.
- To check the colour coding of LT/HT connections.
- To check the colour of Oil.
- To check the locking Washers at the end of HT/LT eye bolts.
- Power Frequency High Voltage Test
- This test is intended to check the adequacy of main insulation to earth and between windings.
- Induced Over Voltage withstand Test
- To check the insulation of HT & LT winding and the insulation between different turns of winding.
- Turn Ratio Test
- This test is carried out to ensure the correctness of Voltage Ratio of Transformer between HT & LT windings on each tapping.
- The voltage ratio of transformer is equal to the turn ratio therefore to verify the voltage ratio we check the turn ratio.
- Measurement of No Load Losses
- This test is carried out to check the quality of the silicon steel sheet (core) used in the transformer.
- No Load losses are very important in this respect that these are permanent and are independent of load.
- These losses should be as minimum as possible and this can be ensured by using good quality silicon steel sheet.
- Measurement of Load Losses & Impedance
- In order to ensure the quality of copper, copper losses are measured.
- Copper losses comprises the sum of I2R losses in the winding and the stray losses due to eddy current in conductor, clamps and tank.
- Good quality copper not only increases the life of transformer but also reduces the system losses.
- As the stray losses vary with the frequency therefore it is important to give the supply to transformer at rated frequency.
- In distribution transformers stray losses are usually negligible.
- Bird Protection Test
- To prevent flashover caused by large birds, transformer cover shall be effectively coated with a weather proof permanent insulation material having a dry dielectric withstand voltage of not less than 8kV.
- Verification of Vector Group
- There are different types of connections according to which, limbs of HT/LT windings are connected. WAPDA has adopted DYn-11 and to verify this, vector group test is carried out.
- Tank Pressure Test
- Lot of welding is involved in the fabrication & manufacturing of transformer due to which there are welding joints at top, cooling tubes & base which can cause leakage/seepage of Oil.
- In order to ensure no leakage/seepage of Oil during normal operation of transformer, pressure test is conducted.
Thursday, 18 July 2013
Routine Tests of Transformer and their Purpose
Subscribe to:
Post Comments (Atom)
No comments:
Post a Comment